Output voltage regulation: Battery Mode - PWM sine wave 115V +/-5%
Output frequency regulation: Line Mode - Passes line frequency of 60Hz +/-10%; Battery Mode - Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type: 8x NEMA 5-15R
Overload protection: 10A input circuit breaker
Input:
Maximum input amps: 8.5 A
Input connection type: NEMA 5-15P
Input cord length: 6 ft. / 1.8 m
Recommended electrical service: 120V 15A
Battery:
Full load runtime: 3.5 min. (900W)
Half load runtime: 13 min. (450W)
Typical battery lifespan: 4~6 years (depending on usage)
Battery recharge rate: 2~8 hours to 90%
Voltage Regulation:
Voltage regulation description: Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using battery power, during brownouts to 75V and overvoltages to 147V
Overvoltage correction: Input voltages between 128VAC and 147VAC are reduced by 12%
Brownout correction: Input voltages between 93VAC and 107VAC are boosted by 14%
Severe brownout correction: Input voltages between 75VAC and 92VAC are boosted by 30%
Surge / Noise Suppression:
AC surge suppression: 480 joules
AC suppression response time: Instantaneous
Dataline suppression: Tel/DSL or Ethernet
EMI / RFI AC noise suppression: Yes
Communications:
Network monitoring port: DB9 and USB
WatchDog compatibility: Compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot of application/OS or hard power off/on reboot of connected equipment; ideal for unattended kiosk applications
Line / Battery Transfer:
Transfer time from line power to battery mode: 2~4 milliseconds
Low voltage transfer to battery power: Switches to battery power as line voltage decreases to 75V or less, switches back to AC mode as line voltage increases to 79V or higher
High voltage transfer to battery power: Switches to battery mode as line voltage increases to 147V or higher, switches back to AC mode as line voltage decreases to 143V or lower
Certifications: Tested to UL1778 (USA), CSA (Canada), NOM (Mexico), Class B (EMI), FCC part 68 and Industry Canada (US & Canada)
Special Features:
Cold Start: Yes, inverter can be "cold started" to enable temporary AC output during a power failure
Appearance: Attractive black color scheme
Physical:
Material of construction: ABS
Form factors supported: Rack/Tower
Cooling method: Convection
Dimensions (WxDxH): 3.5 x 10.5 x 17.25 inch / 8.9 x 26.7 x 43.8 cm